TALK TO OUR EXPERTS

Contact, informations, support and knowledge.

TTA Solar
  • TTA Solar test meter kit pv installation record electrical measurement connection

TTA Solar

$2,600.00

Photovoltaic Measuring Instrument

TTA Solar is a state-of-the-art photovoltaic measuring device.

Perfected over the last 30 years, technical capabilities are unmatched making TTA Solar a market pioneer. TTA Solar provides earth ground resistance, insulation resistance, electric continuity, cut-off voltage, and string short circuit current measurements.

SKU: 10000070000 Category:
000

FEATURES

  • Updated CEI 82-85 Norm; V1 (2001)
  • Simultaneous measurements with single button
  • Automated compiling of test certificate (D.M. 19/2007)
  • Radio solar radiation and radio temperature measurements
  • Insulation resistance
  • Single-phase and three-phase current (by pliers transducers)
  • Single-phase and three-phase voltage
TTA Solar
TTA Solar provides earth ground resistance, insulation resistance, electric continuity, cut-off voltage, and string short circuit current measurements.
Brand: TTA, Inc.
Manufacturer: TTA, Inc.
Model: TTA Solar
Product ID: 10000070000
$2600.00 New

AC SINUSOIDAL 50HZ SINGLE-PHASE AND THREE-PHASE VOLTAGE MEASUREMENT

Range 0 ÷ 600 VAC
Resolution 0,1 VAC
Basic Accuracy ± 0,5 rdg ± 3 dgt

DC VOLTAGE MEASUREMENT

Range 0 ÷ 1000 VDC
Resolution 0,1 VDC
Basic Accuracy ± 0,5 rdg ± 3 dgt

AC SINUSOIDAL 50HZ AND DC SINGLE-PHASE AND THREE-PHASE CURRENT MEASUREMENT (WITH SERIES PLIERS ADAPTERS)

Range 0 ÷ 40 A ; 0 ÷ 400 A
Resolution 0,01 A ; 0,1 A
Basic Accuracy ± 1 rdg ± 3 dgt

AC SINUSOIDAL 50HZ THREE-PHASE POWER MEASUREMENT

Range 0,1 ÷ 42 kW
Resolution 0,1 kW
Basic Accuracy ± 2 rdg ± 5 dgt

TEMPERATURE MEASUREMENT

Range 0 ÷ 100 °C
Resolution 0,1 °C
Basic Accuracy ± 1 rdg ± 2 dgt

RADIATION MEASUREMENT

Range 250 ÷ 1500 Wm-2
Resolution 1 Wm-2
Basic Accuracy ± 2,5 rdg ± 2dgt

DC INSULATION RESISTANCE (250, 500 AND 1000V)

Automatic Range 0 ÷ 200 MΩ
Resolution 0,01 MΩ
Basic Accuracy ± 3 rdg ± 3 dgt

CONDUCTORS CONTINUITY TEST (PROTECTION AND EQUIPOTENTAL)

Range 0 ÷ 100 Ω
Resolution 0,01 Ω
Basic Accuracy ± 3 rdg ± 4 dgt
Test current greater than 200 mA signaled by an acoustic signal

EARTH GROUND RESISTANCE MEASUREMENT FOR TT SYSTEMS (RLOOP METHOD, FAULT LOOP), DIRECTLY IN SOCKET (OR ALSO ON ELECTRICAL SCATTERER/GROUNDS) WITHOUT CAUSE DIFFERENTIAL ELECTRIC SWITCH INTERVENTION ≥ 30 mA

Automatic Range 0 ÷ 2000 Ω
Resolution 1 Ω
Test current about 15 mA
Basic accuracy ± 5% rdg ± 1dgt
Nominal voltage 230 V, 50/60 Hz

OTHER FEATURES

Power supply Pb battery with high rechargeable capacity 6 V 3,4 Ah
Graphic display with backlight
Memory 2000 total location
Connection USB
Double communication between units, hourly synchronization and via radio RF at 2400 bit/s
Pollution level IP40
Automatic turning off after 15 minutes
Dimensions about 9,45×10,63×6,69 in
Weight 855,39 lb
In compliance with CEI EN 61010-1 for CAT IV 600 V (CAT III 1000 V) and CEI EN 61557 Norms

RELEVANT LEGISLATION

CEI 82-25 V1 2011, CEI 82-25 ED 2010, CEI 64-8 E IEC 60364, CEI EN 62446 ED 2010

INCLUDED ACCESSORIES

Data download software with USB cable
alibration Certificate
Battery charger

ACCESSORIES ON DEMAND

Cable connection kit with transportation bag